Enclosure-Type Distribution Automation Feeder Terminal
ZT-F30X
The ZT-F30X Distribution Automation Feeder Terminal Unit is a remotely located terminal of the distribution automation system, independently developed against the backdrop of the construction and development of smart grids. Adhering to a distributed and modular design philosophy, this device comprehensively analyzes the requirements of distribution networks for information acquisition and control. It incorporates highly reliable measurement and control circuits, as well as high-speed, strongly anti-interference industrial fieldbus network technology. Suitable for automation projects in urban, rural, and enterprise distribution networks, this device accomplishes monitoring, control, protection, and communication functions for ring main units and pole-mounted switches. In coordination with distribution sub-stations and main stations, it realizes normal monitoring of distribution lines, as well as fault identification, isolation, and restoration of power supply to non-fault sections, thereby enhancing power supply reliability and reducing fault handling time.
Main functions and characteristics

1) Electrical parameter acquisition: Real-time collection of electrical parameters such as voltage, current, zero-sequence voltage, zero-sequence current, power, power factor, and frequency.

2) Switch status monitoring: Monitor the open and closed states of circuit breakers, load switches, isolating switches, and other equipment.

3) Short-circuit fault detection: Detect short-circuit and ground faults in the line, automatically or manually isolate the faulty section, and reduce the scope of power outages.

4) Remote opening and closing: Control the opening and closing operations of circuit breakers or load switches via remote commands.

5) Self-Diagnosis and Maintenance: Automatically detect the equipment status, promptly identify faults, and support remote upgrades and maintenance.

6) Sequence of Events (SOE) recording: Record the precise time sequence of events such as switch position changes and protective actions.

7) Communication Function: Exchange data with the main station or other terminals, and support multiple communication protocols such as IEC60870-5-101/104, DNP3, etc.

8) Alarm function: Trigger local and remote alarms when abnormalities are detected (such as overcurrent, overvoltage, communication interruption,etc.).

9) Intelligent load management: Optimize load distribution based on load demand and price signals.

Technical parameter
  • 1. Environmental Conditions
    Operating temperature: -40°C - 70°C, relative humidity: 10% - 100%
  • 2. Operating Power Supply
    220V dual power supply, the power supply module is capable of simultaneously providing operating power to the terminal, communication equipment, line loss collection module, and switch for opening and closing operations.
  • 3. Measurement and Control Capacity
    1) Telemetry: Collect 2 line voltages or 3 phase voltages, collect three-phase current, zero-sequence current, and zero-sequence voltage.
    2) Tele signaling: Not less than 3, including switch closed position and not stored energy, etc.
    3) Tele control: 2 channels (closing and opening).
    4) Line loss collection for 1 circuit.
  • 4. Measurement Accuracy
    Current,Voltage: Class 0.5
    Power: Class 1
  • 5. Communication Interface
    Equipped with 2 RJ45 Ethernet ports, 2 RS-232 maintenance serial ports, and other external interfaces.
  • 6. Communication Protocol
    1) Complies with the 101 and 104 communication protocols of the DL/T 634 standard.
    2) Complies with the latest implementation details of the State Grid Corporation for the application of DL/T634.5101-2002 and DL/T634.5104-2009 in distribution automation systems.
    3) Complies with the latest parameter configuration specifications for distribution automation terminals of the State Grid Corporation.
    4) The wireless communication unit supports standard 5G.
  • 7. Terminal Power Consumption
    Total power consumption≤30VA
  • 8. Backup Power Supply Method
    Lead-acid battery/ Lithium battery/ Supercapacitor
  • 9. Interface Method
    Aerospace Connector
  • 10. Mean Time Between Failures(MTBF)
    ≥50000h
  • 11. Installation Method
    Pole or Tower Mounting